aboutsummaryrefslogtreecommitdiffstats
path: root/config/example-extras.cfg
diff options
context:
space:
mode:
Diffstat (limited to 'config/example-extras.cfg')
-rw-r--r--config/example-extras.cfg24
1 files changed, 24 insertions, 0 deletions
diff --git a/config/example-extras.cfg b/config/example-extras.cfg
index f5f6bdb4..89279da9 100644
--- a/config/example-extras.cfg
+++ b/config/example-extras.cfg
@@ -1036,6 +1036,30 @@
#htu21d_report_time:
# interval in seconds between readings. Default is 30
+# LM75/LM75A two wire (I2C) connected temperature sensors.
+# These sensors have range up to 125 C, so are usable for e.g. chamber
+# temperature monitoring. They can also function as simple
+# fan/heater controllers but this mode is not used here.
+#[temperature_sensor my_sensor]
+# See the "temperature_sensor" section below for a description of its
+# parameters. The parameters below describe LM75 family sensor parameters.
+#sensor_type:
+# Must be "LM75"
+#i2c_address:
+# Default is 72 (0x48). Normal range is 72-79 (0x48-0x4F) and the 3 low
+# bits of the address are configured via pins on the chip (usually
+# with jumpers or hard wired).
+#i2c_mcu:
+# MCU the sensor is connected to. Default is the primary mcu.
+#i2c_bus:
+# The I2C bus the sensor is connected to. On some MCU platforms the default
+# is bus 0. On platforms without bus 0 this parameter is required.
+#i2c_speed:
+# The I2C speed (in Hz) to use when communicating with the sensor. Default
+# is 100000. On some MCUs changing this value has no effect.
+#lm75_report_time:
+# interval in seconds between readings. Default is 0.8, with minimum 0.5
+
# Generic heaters (one may define any number of sections with a
# "heater_generic" prefix). These heaters behave similarly to standard
# heaters (extruders, heated beds). Use the SET_HEATER_TEMPERATURE